fix(grafana): no false DATA SOURCE ISSUE page when influxdb restarts (#1682) - #1683

Merged
groupsky merged 2 commits into
masterfrom
fix/1682-grafana-wait-influxdb
Oct 11, 2026
Merged

groupsky merged 2 commits into
masterfrom
fix/1682-grafana-wait-influxdb

Conversation

@groupsky

@groupsky groupsky commented Oct 11, 2026 •

Copy link
Copy Markdown
Owner

Fixes #1682.

Why a page was sent although execErrState: OK

Grafana 9.5 logs from the 2026-10-11 deploy:

  1. 11:00:00 tick: InfluxDB was still opening its store, so the queries failed. execErrState: OK turned this into Normal. No page came from this step.
  2. InfluxDB began to answer at 11:00:04. The heat pump query (current_power, phase B, last 2 min) then ran without error but got no rows. The writers had not yet back-filled the minutes when InfluxDB was down. The data is there now, but it was not there at that moment.
  3. noDataState: NoData put the rule into the NoData state. In Grafana 9.5, NoData does not wait for for:. It is sent at once as an alert named DatasourceNoData, and telegram-bridge prints that as "📵 DATA SOURCE ISSUE" (docker/telegram-bridge/src/message-utils.js).
  4. Both "Термопомпа не работи" (old UI rule 3A5nIop4k) and "Термопомпа не работи (Webhook)" did this, so 2 pages came.

Changes

  1. grafana waits for influxdb: condition: service_healthy. InfluxDB already has a real healthcheck: /health on port 8086. That port opens only after the store is open, and the 300 s start period covers slow opens. This is the smallest way to do it; a wait loop in Grafana's entrypoint would do the same job with more code. Limits:
    • The wait works only when compose starts both in one up, as a deploy that recreates both does. After a reboot, Docker's restart policy does not wait. Change 2 covers that case for the heat pump rule.
    • deploy.sh uses up --no-deps. If only grafana changes, compose v2.18 does not wait. If both change, it waits up to ~300 s, which is inside COMPOSE_TIMEOUT=600.
    • The infrastructure CI test now starts grafana ha with --no-deps. That test needs only the ingress network, and InfluxDB cannot start in that job (its bind-mounted data dir is owned by root). It could not start before this PR either; nobody saw it because nothing waited for it.
  2. The heat pump "not working" rule gets noDataState: Alerting. In 9.5 the Alerting state does wait for for: 15m. A short no-data gap after a restart stays silent. If no rows come back for more than 15 min, the rule still pages under its own title. A full InfluxDB outage, where queries fail, is still seen through the rules that have execErrState: Alerting (boiler controller, sunseeker). Change 1 alone is not enough: the empty window comes from the writers back-filling late, not from Grafana starting early.
  3. 3 old UI-made rules are deleted with a deleteRules file (same way as delete-boiler-manual-mode-alert.yaml). They copy provisioned rules, so each alert was sent twice. Before the delete, all 9 rules in that folder were exported on the host (full rows from grafana.db, plus a copy of the DB file). There is no Grafana admin login on the host, so the Grafana API could not be used.

Old "General Alerting" rules (UI-made, not in the repo)

Contact point: every rule below, and every twin, has no labels that match a route, so all of them use the default telegram-webhook.

Legacy uid Title Provisioned twin Query Threshold for Contact Action
3A5nIop4k Термопомпа не работи webhook-3A5nIop4k same (*) same (<30 W) same 15m same deleted
lA5nSTtVk Main Power alert webhook-lA5nSTtVk same same (>10 kW) same 5m same deleted
z157Sot4z Water pump power alert webhook-z157Sot4z same same (>1 kW) same 15m same deleted
xjXziW_4k Термопомпа претоварена (webhook-lA5nSTt4k is close) 15 min window, not 10 min >1000 W, not >3000 W 15m, not 10m same kept
3057STtVkz AC alert webhook-3057STtVkz other (min/max, not median) 210/248 V, not 207/253 V 0, not 4m same kept
RJcnSop4z External alert none – – 5m default kept
rA5nSotVkz Temperature alert none – – 5m default kept
j05nSotVz Humidity alert none – – 5m default kept
eAc7ITtVk Output alert none – – 5m default kept

(*) The only differences: the expression step uses the old datasource id -100 instead of __expr__ (both mean "expression"), and 3A5nIop4k keeps an unused raw-query text from an old editor mode (rawQuery: false).

For the owner: the 6 kept rules are still only in the Grafana DB. xjXziW_4k alerts at >1000 W but its message says 3000 W, and it keeps noDataState: NoData.

Not changed (said here instead of built)

Other provisioned rules still use noDataState: NoData. The only one with a short window is Main Power (Webhook), with a 5 min window. If InfluxDB is killed and needs ~200 s to open, that window could also be empty for a moment. Its Alerting state means ">10 kW", so noDataState: Alerting would be a wrong page there. If it ever fires on a deploy, it needs its own fix.

Done-when proof

The deploy check (both containers recreated, then the Telegram send log) will be added as a comment on #1682 after merge.

…1682)

- grafana waits for influxdb to be healthy (depends_on service_healthy)
- heat pump 'not working' rule: noDataState Alerting, so a short no-data
  gap waits for 'for: 15m' instead of paging at once
- delete 3 old UI-made rules that duplicate provisioned ones